Technology functions
CPU 317T: Technology Functions
6-136 A5E00251798-03
ErrorID
Error message Description / to correct or avoid error
8053 Invalid instance DB Faulty instance DB of the technology function (wrong
length, for example.)
8083 DB is not a technology DB
The DB specified at input parameter Axis or the
technology DB were not found.
8084 Invalid technology DB A technology object does not exist in the PLC for the
technology DB specified at input parameter Axis.
Download the current technology to the PLC, or
change the DB number at input parameter Axis.
The user has written invalid data to the technology DB
specified at input parameter Axis.
In "Technology Objects Management", delete and then
recreate the technology DB.